DALI Test
Self Test (ST) / Manual Test (MT)
Important
It is recommended that the module is installed by a qualified electrician ensuring the installation complies with the necessary standards. Emtrons
Technologies Co accepts no responsibility for injury, damage or loss, which may arise as a result of incorrect installation, operation or maintenance.
The converter requires an un-switched supply for charging the battery and a switched supply if the unit is being used for maintained operation.
ISOLATE BOTH MAINS SUPPLIES AND DISCONNECT THE BATTERY BEFORE INSTALLATION OR MAINTENANCE.
System status indication
Notes: - After repairing a service fault, press and hole the test button for more than 2 seconds to reset the flashing indicator light to green.
-The above instructions apply to Emtrons products that comply with lEC 61347-2-7 2021.
LED indicator
LED indication
Green permanent
Green slow flash (4s on, 1s off)
Green medium flash (2s on, 2s off)
Green fast flash (0.5s on, 0.5s off)
Red Slow flash (4s on, 1s off)
Red fast flash once, then pause (0.5s on, 0.5s off, 4s pause)
Fast flash twice, then pause (0.5s on, 0.5s off, 4s pause)
Fast flash 3 times, then pause (0.5s on, 0.5s off, 4s pause)
Fast flash 4 times, then pause (0.5s on, 0.5s off, 4s pause)
Fast flash 5 times, then pause (0.5s on, 0.5s off, 4s pause)
Green and Red Off
Power on and System OK
Charging
Duration test and 5 days indication following completion of test
Function test
The battery temperatureis out of range
Battery not connected or short-circuited
Low battery capacity
Charge circuit fault
LED driver circuit fault
LED lamp fault
Power off
System Status
The following information is only about the ST
30 seconds function test
3 minutes function test
30 minutes function test
duration test(rated duration=1/2/3 hours)
Once within 2 seconds
twice within 2 seconds
3 times within 2 seconds
4 times within 2 seconds
Function test and Duration can also be initiated manually by pressing the test button when the mains supply is on, as follows:
Button Test
Once the self test system (STS) is powered up, it will automatically initiate a self-test and diagnostics as follows:
At every times: Check for battery disconnection, battery capacity, charge board fault, LED lamp fault and LED driver fault.
Every month: Performs 3 minutes functional test.
Every year: Performs a rated duration test.
At 30-day intervals the STS will automatically perform a function test by forcing the STS into emergency operation for 3 minutes.
Once a year the STS will automatically carry out a full duration test by forcing the STS into emergency operation for its rated emergency duration.
Upon initial power-on, random automatically-initiated rated duration is generated, so the start times of the tests are set automatically to ensure
random testing of the STS.